Installation
Instructions
Bradley Drench
Shower Horizontal Supply
Model E1
Table of Contents
Pre-Installation Information
Installation Instructions
Assembly of Components
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
3
4
4
IMPORTANT
This equipment should be inspected,
tested, and recorded weekly to maintain
proper operation.
Main water supply to the eye wash
should be “ON” at all times.
This installation manual and parts list
should be filed by the building owner’s
maintenance department.
Ref. G; EN 98-579
PO. Box 309, Menomonee Falls, WI USA 53052-0309
PHONE (414) 251-6000 FAX (414) 251-5617
Page 1 of 4
Bradley Drench Shower Horizontal Supply
Model No.
Installation Instructions
Pre-Installation Information
Operation
The drench shower is easily activated by pulling the triangular pull rod downward, and
deactivated by pushing the triangular pull rod upward.
Components
Showerhead: The corrosion-resistant stainless steel showerhead has a 254 mm (10”) diameter.
Shower Valve: The 1” IPS stay-open valve is operated by a stainless steel pull rod with a
triangle handle.
Water Supply: Water supply connection is 1” BSP horizontal.
Pipe and Fittings: Pipe and fittings are galvanized steel, coated with
safety yellow.
Check Contents
Separate all parts from packaging and check each part with Figure 2 and the Parts List on
page 4. Make sure all parts are accounted for before discarding any packaging material. If any
parts are missing, do not attempt to install your Bradley Drench Shower until you obtain the
missing parts.
Bradley Drench Shower Warranty
Bradley Corporation warrants to commercial and institutional purchasers only each fixture free from defects in
material and workmanship under normal use and service upon the following terms and conditions:
1. We will replace, without charge, any part which proves to be defective within one year from date of our
invoice at our option, F.O.B. Menomonee Falls, Wisconsin.
2. This warranty does not cover installation or any other labor charge and does not apply to fixtures which have
been damaged by accident, abuse or improper maintenance.
3. The repair or replacement of the defective fixtures as stated in this warranty shall constitute the sole remedy
of the purchaser, and the sole liability of the Bradley Corporation under this warranty. Bradley Corporation
shall not otherwise be liable under any circumstances for incidental, consequential or indirect charges caused
by defects in fixtures or any delay in the repair or replacement thereof.
4. This warranty extends only to commercial and institutional purchases and does not extend to any others,
including consumer, customers of commercial and institutional purchasers.
5. This warranty is in lieu of all other warranties expressed or implied, including any implied warranty of mer-
chants ability or fitness for a particular purpose, or otherwise.
6. Bradley emergency fixtures are to be used as a supplement to first aid treatment. Bradley Corporation cannot
guarantee
when used this emergency equipment will prevent serious injury or the aggravation of existing
or prior injuries. No other warranties, expressed or implied are authorized, provided or guaranteed by
Bradley Corporation.
Bradley Corporation l
Ref. G; EN 98-579
2
Bradley Drench Shower Horizontal Supply
Model No.
Installation Instructions
Installation Instructions
Supplies Required:
l
l
l
l
Pipe sealant
Piping to 1” BSP water supply inlet on unit
Adequate supply pipe supports
Minimum 102 mm (4”) drain to accommodate 115 liters per minute discharge for drench
shower waste
Step 1: Assemble drench shower
NOTE: Flush the water supply line before beginning
installation.
1. Assemble drench shower components as shown
in Figure 2 on page 4.
2. Apply pipe sealant or tape (supplied by installer)
to all male-threaded pipe joints.
NOTE: Use a strap wrench around the pipes when
tightening to prevent mm-ring.
3. The bottom edge of the showerhead should be
2134 mm
from the floor.
Step 2: Connect water supply
Figure 1
IMPORTANT: Do not rely on Bradley’s
Drench Shower to support
supply piping.
1. Connect water supply piping to
BSP inlet on unit (piping supplied by installer).
Provide adequate supports (supplied by installer) for supply pipe using pipe hangers or
other means.
2. Mount safety sign to wall or pipe using sign mounting hardware supplied.
3. Open water supply lines. Test for leaks and adequate water flow.
Installation Instructions continued..
3
Bradley Corporation
l
G; EN 98-579
Bradley Drench Shower Horizontal Supply
Model No.
Installation Instructions
1” BSP SUPPLY INLET
Assembly of
i
Figure 2
Parts List
ITEM
4c
PART NO.
DESCRIPTION
SCREW
DESCRIPTION
PART NO.
ITEM
2
1
BALL VALVE
1
1
ADAPTER
LOCKWASHER
4D
WASHER
4E
1
4
1
1
1
1
1
BALL VALVE
HANDLE
DIFFUSER PADS
SIGN-MOUNTING HARDWARE
4F
128-129
140-720
STOP
1
PULL ROD
LONG
PIPE 1” IPS
8
r
2
3
1
EMERGENCY TAG
SAFETY SIGN
BSP ADAPTOR
JAM NUT
1
90” STREET ELBOW 1’ IPS
STN. STL SHOWERHEAD ASSY.
SHOWERHEAD SHELL
DIFFUSER
189-723
1
1
1
1
8’
9
4
1
153-298
110-214
4A
187-053
155-008
1
10
l
Not Shown
Bradley Corporation
l
Ref. G; EN 98-579
4
|